Copper Compression Cable Lug According To DIN 46235

DIN 48201, DIN 57295

Share on facebook
Share on twitter
Share on linkedin
Share on print
Share on whatsapp

Description

For Copper Conductors.

Material

Copper, DIN 40500/2, F-25.

Surface:

Tin-plated. *Inside diameter adapted according to DIN 57295. Sector-shaped conductors must be rounded with round-forming dies.
Cat. #Ref.Conductor
Diameter
׳²ֲ³ײ»ֲœ mm
Die
code
No.
DimensionsNo.
of
compresns
wght
100
Pcs.
Kg.
(~)
#
units
(box)
DINLarge/
Small
5729548201/1
Solid/Strand.
d1lbd2mech/hydr.
1013002406x62.75/3.05 3.8 24 8.5 6.51/-0.41000/
100
10130024110x6 3.55/4.16 4.5 27 96.51/- 0.41000/
100
10130024210x8 3.55/4.1 8 4.5 36 13.0 8.5 2/- 0.4800/
100
*10130024310x10 3.55/4.1 8 4.5 36 17.0 10.52/- 0.8800/
100
101300244 16x6 4.5 8 5.5 36 136.5 2/- 1.4250/
50
101300245 16x8 4.5 8 5.5 3613.0 8.52/- 1.4250/
50
10130024616x10 4.5 8 5.5 36 17.0 10.52/- 1.4250/
50
*10130024716X13250/
50
10130024925X6200/
-
101300250 25x8 5.6-6.5 -/6.310 7.0 38 16.0 8.5 2/- 1.7200/
-
10130025125x10 5.6-6.5 -/6.310 7.0 38 17.0 10.5 2/- 1.7200/
-
*10130025225x13 5.6-6.5 -/6.3107.0 38 19.0 13.0 2/- 1.7200/
-
10130025635X6150/
-
10130025735x8 6.6-7.5 -/7.5128.2 42 17.0 8.52/- 3.2150/
-
101300258 35x10 6.6-7.5 -/7.512 8.2 42 19.0 10.5 2/- 3.1150/
-
10130025935x136.6-7.5 -/7.512 8.2 42 21.0 13.0 2/- 3.0150/
-
*10130026035x17 6.6-7.5 -/7.512 8.242 26.0 172/- 3.3100/
-
10130030350X6100/
-
101300292 50x8 7.7-8.6 -/9.01410.0 52 20.0 8.5 3/- 5.3100/
-
101300261 50x10 7.7-8.6 -/9.014 1052 22.0 10.53/- 5.2100/
-
10130026250x137.7-8.6 -/9.014 10.0 52 24.0 133/- 5.1100/
-
*10130026350x17 7.7-8.6 -/9.014 10.0 52 28.0 17.0 3/- 4.850/
-
10130030270X6100/
-
10130029370X8100/
-
101300264 70x10 9.3-10.210.5/1611.5 5524.0 10.5 3 -/6.8100/
-
10130026670x139.3-10.210.5/1611.555 2413.03 -/6.5100/
-
*10130026770x17 9.3-10.2 10.5/1611.5 55 30.0 17.0 3 -/6.6100/
-
10130030195X650/
-
10130029495X850/
-
101300268 95x10 11.0-12.0 12.5/1813.56528.0 10.5 4 2/9.750/
-
101300269 95x1311.0-12.012.5/1813.56528.0 13.0 4 2/9.4 50/
-
*10130027095x17 11.0-12.0 12.5/1813.5 6532.0 17.0 42/9.8 50/
-
101300304120X650/
-
101300300120X850/
-
101300271120x10 12.5-13.514.0/2015.5 70 32.0 10.5 4 2/11.650/
-
101300272 120x1312.5-13.5 14.0/20 15.5 7032.0 134 2/11.2 50/
-
101300273 120x1712.5-13.5 14/2015.5 7032.0 17.0 4 2/10.9 50/
-
101300295150X850/
-
101300274150x1013.9-15.0 15.7/2217.0 7834.0 10.5 4 2/16.7 50/
-
101300275 150x13 13.9-15.0 15.7/22 17.07834.0 13.0 4 2/16.2 50/
-
101300276150x1713.9-15.0 15.7/22 17.0 7834.017.042/16.050/
-
101300277185x10 15.5-16.817.5/2519.0 82 37.0 10.552/19.5 50/
-
101300278185x13 15.5-16.8 17.5/25 19.0 82 37.0 135 2/19.2 50/
-
101300279 185x1715.5-16.8 17.5/25 19.0 82 37.0 17.0 5 2/18.9 50/
-
101300280240x1017.8-19.2 20.2/2821.5 92 42.0 10.5 2/28.9 30/
-
101300281 240x13 17.8-19.220.2/28 21.592 4213.0 2/27.9 30/
-
101300282240x1717.8-19.2 20.2/28 21.592 42.0 17.0 2/28.530/
-
101300283300X1025/
-
101300284300x13 20.0-21.6 22.5/32 24.5 10048.013.0 2/33.925/
-
101300285300x1720.0-21.6 22.5/3224.5 10048.017.0 2/33.3 25/
-
101300290300X21-/
-
101300286400X1310/
-
*101300286 400x1722.9-24.6 -/3826.0 115 55.0 17.0 3/70.8 10/
-
101300288500X1310/
-
101300289 500x17 25.7-27.6 -/422912560.0 17.0 3/84.710/
-
101300298625X1710/
-
101300299625X2110/
-

User Instructions

The compression cable lugs are marked with a code number in front of the logo (roughly corresponding to the outer diameter of the compression sleeve). The required compression die is selected in accordance with this code number. For hexagonal compressions made with hand-operated mechanical compression tools, browned dies (black) are to be used for copper cable lugs, whereas aluminium cable lugs require electro-galvanized dies (white). For hydraulic compression tools there is no differentiation of dies for copper or aluminium cable lugs. The compression sleeve of aluminium cable lugs is pre-filled with compression compound which must not be removed before the compression, neither completely nor in part. Any compression compound escaping during the compression should be wiped off. Copper cable lugs are not pre-filled with compression compound. Assembly Instructions
  1. Clean the conductor or cable ends with a wire brush to remove dirt and oxidation.
  2. Insert conductor or cable ends into the compression sleeve up to the stop.
  3. Before proceeding, make sure that the code number on the cable lug matches that on the compression die.
  4. Cable lugs are compressed by starting from the plate end and working out toward the sleeve end. The number of compressions is marked on the sleeve. It is important to make the specified number of compressions.